Megger MIT525 Insulation Resistance Tester Description
The Megger MIT525 insulation resistance tester is a great tool for identifying the efficacy of the electrical insulation of a product. The device is highly safe to use because it comes with double-insulated leads in a tough, fire proof carry case. It also comes with five preset voltage ranges, which assist user interface. We offer the MIT525 to rent for as little as £90 per week.
Features and Benefits
- IR, Timed IR, DAR, PI, DD, SV and ramp diagnostic tests
- High noise immunity – 3 mA (5 kV and 10 kV) 6 mA (15 kV) of noise rejection
- Dedicated voltmeter function (30 V to 660 V)
- Advanced memory, on screen recall and real time clock for date/time stamped results
- Download of on-board results via USB interface
- Recorded temperature (measured by independent instruments) can be saved with test result
Product Specs
- AC voltage (autoranging): 5 kV, 10 kV: 90-264 V rms, 47- 63 Hz 100 VA, 15 kV: 90-264 V rms, 47- 63 Hz 200 VA
- Battery charge time: 2.5 hours deep discharge, 2 hours normal discharge
- Battery life: 11.1 V, 5.2Ah Li-ion batteries, meet IEC 62133:2003, MIT1525 has 2 battery packs. 6 hours (typical) continuous testing at 5 kV with a 100 MW load
- Test voltage: 250 V, 500 V, 1000 V, 2500 V, 5000 V, VL
- Lock test voltage: 40 V to 1 kV in 10 V steps, 1 kV to 5 kV in 25 V steps, 5 kV to 15 kV in 25 V steps
- Test voltage accuracy: +4%, -0%, ±10 V nominal test voltage at 1 GΩ load (0°C to 30°C)
- Resistance range: 10 k to 15 TΩ @ 5 kV, 10 k to 35 TΩ @ 10 kV, 10 k to 35 TΩ @ 15 kV
- Guard terminal performance: Guards out parallel leakage resistance down to 250 kΩ with a maximum additional resistance error of 1% with a 100 MΩ load
- Analogue display: 100 kΩ to 10 TΩ
- Digital display: 10 kΩ to 305 TΩ
- Short circuit/charge current: 3 mA @ 5 kV, 10 kV, 15 kV
- Insulation test: Alarm: 100 kW to 10 GW
- Capacitor charge: <3 s/μF at 3 mA to 5 kV
- Capacitance range: With test voltage set above 500 V: 10 nF to 25 μF
- Capacitance measurement accuracy: ±10% ±5 nF
- Current range: 0.01 nA to 6 mA
- Current accuracy: ±5% ±0.2 nA at all voltages (23 °C)
- Interference: 3 mA from 450 V to 5 kV
- Voltmeter range: 30 V to 660 V ac or dc, 45Hz – 65Hz
- Voltmeter accuracy: ±3%, ±3V
- Timer range: Up to 99 minutes 59 seconds, 15 second minimum setting
- Memory capacity: 5.5 hours logging @ 5 sec intervals